Model |
SUN-30K-SG01HP3-EU-BM3 |
SUN-40K-SG01HP3-EU-BM4 |
SUN-50K-SG01HP3-EU-BM4 |
|
Battery Input Data |
|||
|
Battery Type |
Lithium-ion
|
||
|
Battery Voltage Range(V) |
160~800
|
||
|
Max. Charging Current (A) |
50+50
|
||
|
Max. Discharging Current (A) |
50+50
|
||
|
Number of battery input |
2
|
||
|
Charging Strategy for Li-Ion Battery |
Self-adaption to BMS
|
||
|
PV String Input Data |
|||
|
Max. DC Input Power (W) |
39000
|
52000
|
65000
|
|
Max. DC Input Voltage (V) |
1000
|
||
|
Start-up Voltage (V) |
180
|
||
|
MPPT Range (V) |
150-850
|
||
|
Full Load DC Voltage Range (V) |
360-850
|
360-850
|
450-850
|
|
Rated DC Input Voltage (V) |
600
|
||
|
PV Input Current (A) |
36+36+36
|
36+36+36
|
36+36+36+36
|
|
Max. PV ISC (A) |
55+55+55
|
50+50+50
|
50+50+50+50
|
|
Number of MPPT / Strings per MPPT |
3/2
|
4/2
|
4/2
|
|
AC Output Data |
|||
|
Rated AC Output and UPS Power (W) |
30000
|
40000
|
50000
|
|
Max. AC Output Power (W) |
33000
|
44000
|
55000
|
|
AC Output Rated Current (A) |
45.5/43.5
|
60.7/58
|
75.8/72.5
|
|
Max. AC Output Rated Current (A) |
50/47.8
|
66.7/63.8
|
83.4/79.7
|
|
Max. Three-phase Unbalanced Output Current |
60
|
70
|
83.3
|
|
Max. Continuous AC Passthrough (A) |
200
|
||
|
Peak Power (off grid) |
1.5 time of rated power, 10 S
|
||
|
Generator input/Smart load
/AC couple current (A) |
45.5 / 200 / 45.5
|
60.7 / 200 / 60.7
|
75.8 / 200 / 75.8
|
|
Power Factor |
0.8 leading to 0.8 lagging
|
||
|
Output Frequency and Voltage |
50/60Hz; 3L/N/PE 220/380, 230/400Vac
|
||
|
Grid Type |
Three Phase
|
||
|
Total Harmonic Distortion (THD) |
<3% (of nominal power)
|
||
|
DC current injection |
<0.5% In
|
||
|
Efficiency |
|||
|
Max. Efficiency |
97.60%
|
||
|
Euro Efficiency |
97.00%
|
||
|
MPPT Efficiency |
99.90%
|
||
|
Protection |
|||
|
Integrated |
PV Input Lightning Protection, Anti-islanding Protection, PV String Input Reverse Polarity Protection,Insulation Resistor Detection, Residual Current Monitoring Unit, Output Over Current Protection,Output Shorted Protection, Surge protection
|
||
|
Output Over Voltage Protection |
DC Type II/AC Type III
|
||
|
Certififications and Standards |
|||
|
Grid Regulation |
VDE4105, IEC61727/62116, VDE0126, AS4777.2, CEI 0 21, EN50549-1, G98, G99, C10-11, UNE217002, NBR16149/NBR16150
|
||
|
Safety EMC / Standard |
IEC/EN 61000-6-1/2/3/4, IEC/EN 62109-1, IEC/EN 62109-2
|
||
|
General Data |
|||
|
Operating Temperature Range (℃) |
-45~60℃, >45℃ derating
|
||
|
Cooling |
Smart cooling
|
||
|
Noise (dB) |
≤65 dB
|
||
|
Communication with BMS |
RS485; CAN
|
||
|
Weight (kg) |
75
|
||
|
Size (mm) |
527W×894H×294D
|
||
|
Protection Degree |
IP65
|
||
|
Installation Style |
Wall-mounted
|
||
|
Warranty |
5 years
|
||